Upcoming Auctions & Liquidation Sale Event Details, Auctioneers

Event Detail

Click on any image to view larger.

Available Now! 400MW Gas Powered Power Plant

Westinghouse/Siemens W501D5 GAS TURBINE GENERATOR SET: 100MW x 4 units

4 Units Total, Can Be Sold as Individual Units!

Westinghouse/Siemens W501D5 USA

 

Location:  Jungbong-daero,  405 beon-gil,  Seo-gu,  Incheon, South Korea,


Details

4 Units Available! Orderly Negotiated Sale. Contact Josh Schneider at joshs@schneiderind.com for information on pricing.  

Siemens/Westinghouse W501D5 

400MW (60HZ) GAS TURBINE POWER PLANT 

GAS TURBINE GENERATOR SET: 100MW x 4 units 

HZ: 60hz 

Fuel : LNG 

Build in: 1995 

stopped operation : June 2013 

Gas Turbines 

Manufacturer : WESTINGHOUSE(SIEMENS) 

Model Name : W501D5 

Type : Axial Flow 

Power Output : 100, 000 kW(100MW) 

Stages : 4 stage 

Inlet Temp. : 1093 ℃ 

Exhaust Temp. : 530 ℃ 

Exhaust Flow : 1313272 kg/h 

TAC Temp. : 15℃ 

Speed Governor : DEHC 

-Starter System 

Type : Electric Motor 

Capacity : 1530 kW 

Quantity : 1 ea 

-Combustor 

Type : Can-Annular 

Quantity : 14 ea 

-Compressor 

Type : Axial Flow 

Air Mass Flow : 358 N㎥/min 

Inlet Temp. : 15℃ 

Pressure Ratio : 14:01 

Outlet Pressure : 14.462 kg/㎠ 

Stages : 19 stage 

Outlet Temp. : 389 ℃ 

 

2.Generators 

Manufacturer : WESTINGHOUSE(SIEMENS) 

Type : OAC(Open-Air-Cooled) 

Rated Power : 129(143) MW(MVA) 

Power Factor/ short-circuit ratio : 90%/0.695 

Frequency : 60Hz/2pole 

Speed : 3600 RPM 

Rated Voltage/Current : 13.8 kV/5731 A 

Insulation Class : F 

-Exciter 

Speed : 3600 RPM 

Exciter Type : PMG 

Rated Voltage/Current 325 V/1006 A 

Protection Devices : 87G, 59GN, 40, 32, 46, 51V, 60, 25 

Neutral Grounding : NGR 

Bus Bar : IPB(3phases) 

Rotation Direction : CW(Viewed Form Exciter end) 

 

3.Operation hours 

Gas Turbine #1. 37, 566hours(1996.1~2013.6) 

Gas Turbine #3. 39, 800hours(1996.1~2013.6) 

Gas Turbine #4. 41, 541hours(1996.7~2013.6) 

Gas Turbine #5 41, 819hours(1996.7~2013.6) 

 

4.Operation hours from overhaul to stop 

Gas turbine #1: 18, 117 hours 

Gas turbine #3: 17, 098 hours 

Gas turbine #4: 15, 686 hours 

Gas turbine #5: 17, 978 hours 

 

5.Generator serial number 

Generator#1. 93P0621 

Generator#3. 93P0635 

Generator#4. 93P0684 

Generator#5. 93P0695 

 

6.Scope of supply 

Turbine 

Generator 

Control panel(Electric package) 

Switchgear box 

Mechanical room equipment 

Currently installed with target dismantling schedule during early 2017

 

AuctionServices